FM’s VSH Testing – Very Severe Hail
FM Global, a leading commercial building insurer, and its code-approved testing agency subsidiary, FM Approvals, have created a Very Severe Hail (VSH) impact resistance classification that could affect some of the work you do.
FM Global Guidelines
Traditionally, FM Global has recommended its insured building owners use moderate hail (MH) and severe hail (SH) classified roof systems for buildings located in areas FM Global considers to be susceptible to moderate or severe hail impacts. FM Loss Prevention Data Sheet 1-34 ("Hail Damage") provides a map identifying these regions.
In recent years, the insurance industry in the United States has seen an uptick in losses from hail in terms of the number of claims experienced and costs of those claims. A majority of the hail damage occurs to roof systems and other rooftop components.
In the latest version of FM 1-34 (April 2019), FM Global identified a new VSH region encompassing Oklahoma, Kansas, Nebraska, South Dakota, most of Texas, and parts of Montana, North Dakota, Minnesota, Iowa, Missouri, Arkansas, Wyoming, Colorado, and New Mexico.
Per FM Global, this area was classified as a VSH region based on data from the National Oceanic and Atmospheric Administration's National Weather Service and National Center for Environmental Protection's Storm Prediction Center. This data shows a concentration of reports of hail greater than 2 inches in diameter in this geographical region.
Until recently, FM Approvals did not have VSH-classified roof systems available to satisfy its recommendation in the VSH region. In the interim, FM 1-34 recommended using assemblies tested to a Class 4 rating using FM 4473 ("Specification Test Standard for Impact Resistance Testing of Rigid Roofing Materials by Impacting with Freezer Ice Balls").
FM 1-34 indicates aggregate- and paver-ballasted roof systems can be substituted for MH- and SH-classified roof systems in the MH and SH regions. However, FM Global restricts the use of aggregate-ballasted roof systems on buildings taller than 150 feet, or in areas where the design wind speed is 100 miles per hour or greater.
FM has indicated only paver-surfaced roof systems can be substituted for a VSH-classified roof system.
FM 1-34 also contains recommendations for skylights, rooftop HVAC equipment, and other critical outdoor equipment in the MH, SH, and VSH regions.
Hail Classifications
FM Approvals traditionally has tested and classified membrane roof systems for MH and SH impact resistances using FM 4470 ("Approval Standard for Single-Ply, Polymer-Modified Bitumen Sheet, Built-Up Roofs (BUR) and Liquid Applied Roof Assemblies for use in Class 1 and Noncombustible Roof Deck Construction). This is the same test method on which many FM Approvals roof system classifications are based.
Using FM 4470's procedure, MH-classified roof systems withstand a 2-inch-diameter steel ball weighing 1.19 pounds dropped from a height of 81 inches in a section of tubing. This results in an impact energy of about 8 foot-pounds (ft-lbs.) on the surface of the roof system test specimen.
SH-classified roof systems withstand the same 2-inch-diameter steel ball dropped from a height of 141.5 inches, resulting in an impact energy of about 14 ft-lbs. on the surface of the roof system test specimen.
FM Approvals recently updated its impact-resistance test method to include testing for the VSH classification. The new testing involves propelling 2-inch-diameter preformed ice balls at roof system test specimens using an ice ball launcher. The ice balls are propelled at 152 to 160 feet per second, resulting in an impact energy of 53 to 58 ft-lbs. on the surface of the roof system test specimen.
With these higher test standards, new materials, and assemblies are being developed and tested to meet the new ratings. Versico has introduced a new coverboard, DuraStorm, that can achieve the VSH rating. Versico currently has over 150 approved VSH approved assemblies.
FM Global Guidelines
Traditionally, FM Global has recommended its insured building owners use moderate hail (MH) and severe hail (SH) classified roof systems for buildings located in areas FM Global considers to be susceptible to moderate or severe hail impacts. FM Loss Prevention Data Sheet 1-34 ("Hail Damage") provides a map identifying these regions.
In recent years, the insurance industry in the United States has seen an uptick in losses from hail in terms of the number of claims experienced and costs of those claims. A majority of the hail damage occurs to roof systems and other rooftop components.
In the latest version of FM 1-34 (April 2019), FM Global identified a new VSH region encompassing Oklahoma, Kansas, Nebraska, South Dakota, most of Texas, and parts of Montana, North Dakota, Minnesota, Iowa, Missouri, Arkansas, Wyoming, Colorado, and New Mexico.
Per FM Global, this area was classified as a VSH region based on data from the National Oceanic and Atmospheric Administration's National Weather Service and National Center for Environmental Protection's Storm Prediction Center. This data shows a concentration of reports of hail greater than 2 inches in diameter in this geographical region.
Until recently, FM Approvals did not have VSH-classified roof systems available to satisfy its recommendation in the VSH region. In the interim, FM 1-34 recommended using assemblies tested to a Class 4 rating using FM 4473 ("Specification Test Standard for Impact Resistance Testing of Rigid Roofing Materials by Impacting with Freezer Ice Balls").
FM 1-34 indicates aggregate- and paver-ballasted roof systems can be substituted for MH- and SH-classified roof systems in the MH and SH regions. However, FM Global restricts the use of aggregate-ballasted roof systems on buildings taller than 150 feet, or in areas where the design wind speed is 100 miles per hour or greater.
FM has indicated only paver-surfaced roof systems can be substituted for a VSH-classified roof system.
FM 1-34 also contains recommendations for skylights, rooftop HVAC equipment, and other critical outdoor equipment in the MH, SH, and VSH regions.
Hail Classifications
FM Approvals traditionally has tested and classified membrane roof systems for MH and SH impact resistances using FM 4470 ("Approval Standard for Single-Ply, Polymer-Modified Bitumen Sheet, Built-Up Roofs (BUR) and Liquid Applied Roof Assemblies for use in Class 1 and Noncombustible Roof Deck Construction). This is the same test method on which many FM Approvals roof system classifications are based.
Using FM 4470's procedure, MH-classified roof systems withstand a 2-inch-diameter steel ball weighing 1.19 pounds dropped from a height of 81 inches in a section of tubing. This results in an impact energy of about 8 foot-pounds (ft-lbs.) on the surface of the roof system test specimen.
SH-classified roof systems withstand the same 2-inch-diameter steel ball dropped from a height of 141.5 inches, resulting in an impact energy of about 14 ft-lbs. on the surface of the roof system test specimen.
FM Approvals recently updated its impact-resistance test method to include testing for the VSH classification. The new testing involves propelling 2-inch-diameter preformed ice balls at roof system test specimens using an ice ball launcher. The ice balls are propelled at 152 to 160 feet per second, resulting in an impact energy of 53 to 58 ft-lbs. on the surface of the roof system test specimen.
With these higher test standards, new materials, and assemblies are being developed and tested to meet the new ratings. Versico has introduced a new coverboard, DuraStorm, that can achieve the VSH rating. Versico currently has over 150 approved VSH approved assemblies.
- For more information on DuraStorm VSH Coverboard, click here.
- Contact Brian Emert with further questions.
Up Next
August 06, 2020
White EPDM Technology Evolution
Since the introduction of white EPDM roofs in 1987, numerous enhancements have been made to the membrane and system components.
July 23, 2020
The Role of Cover Boards in Commercial Roofing
Cover boards have the unique ability to enhance the overall performance of commercial roof systems.
June 25, 2020
Fleece-Backed Systems: Tough, Durable, Reliable
Over the years, fleece-backed membrane systems have been used due to their superior performance.